Tool · estimate only

Starting surge check

A compressor's start is the steepest climb a generator faces. Type in the figures from the compressor nameplate and the generator's documentation, and this page works out the starting demand as a straight start and with the reduction a soft starter maker publishes, then, if you give a surge rating in kVA, sets both beside it.

This tool needs JavaScript, which is switched off or has not loaded. Nothing you type is sent anywhere; the figures stay in the page.

Your figures

The compressor's rated voltage from its nameplate. The buttons only fill the box; they are not a statement about your supply.

Printed as LRA on the compressor or outdoor unit nameplate. It is not the running figure (RLA) or the fuse size.

The starting current reduction in the soft starter maker's documentation, if it gives one for a comparable starting current. Makers may word it as "up to" or tie it to learning starts, so read that maker's own wording. Leave blank for a straight start.

The surge kVA the generator's documentation gives for the connection you would use. Only a kVA figure is compared. A W or kW figure is real power, so it is shown as entered and not compared.

Estimate

Enter a voltage and the locked rotor amps, then press Check the surge to see the starting estimates.

The formula

starting kVA       = volts × locked rotor amps ÷ 1000
with soft starter  = starting kVA × (1 − reduction ÷ 100)
starting amps      = locked rotor amps × (1 − reduction ÷ 100)
% of rating        = 100 × estimated kVA ÷ surge rating in kVA

The percentage is worked out only when the surge rating is entered in kVA, so both sides are in the same unit. A rating entered in W or kW is shown back as entered and not compared (see the fourth assumption below).

Accepted inputs. These are this tool's own limits, there to catch typos. Voltage 1 to 1,000 V. Locked rotor amps 0.1 to 2,000 A. Reduction 0 up to but not including 100 percent. Surge rating 0.001 to 1,000,000 in the unit chosen. Plain numbers only, with commas allowed only as thousands separators. Results are labelled estimates and show "less than 0.01 kVA" instead of 0.00.

Assumptions

  • Single-phase supply. Volts times amps ÷ 1000 is the apparent power of a single-phase load in kVA. Three-phase equipment needs a different formula, which this check does not use.
  • Locked rotor amps stand in for the starting current. LRA is the current a motor draws at its rated voltage with the rotor held still. This check uses it as the starting current of a straight start. That is a modelling choice, not a measurement.
  • The voltage is fixed. The model uses the voltage you enter and keeps it constant. In practice the voltage at the compressor can sag during a start, which changes the current.
  • kVA is compared with kVA. kW equals kVA times power factor, so a rating in W or kW does not give the kVA limit of a connection. For that reason a W or kW rating is not compared. Use the surge kVA from the generator's documentation for the connection you would use.
  • The reduction is the soft starter maker's figure. It only means something against a comparable starting current. Makers may word it as "up to", or tie it to a starter's learning starts, so read that maker's own documentation for the exact conditions.
  • Other loads are not included. Anything else running on the generator at the same moment adds to the demand.

All results are estimates from your own figures. They are not a prediction that a particular generator will or will not start a particular unit; the generator and soft starter makers' documentation has the final word.

Formula and unit references

These pages support the formula and the two unit conversions (divide by 1000, divide by 100). They are not product claims.

  1. What is the formula to determine the KVA on a Transformer? (Schneider Electric (New Zealand FAQ)) Single-phase kVA from volts and amps, and the link between kVA and kW through power factor.
  2. The International System of Units (SI): SI prefixes (BIPM (International Bureau of Weights and Measures)) Kilo means 10 to the power 3, which is the divide-by-1000 in the formula.
  3. NIST Special Publication 330, section 5 (rules and style for SI quantities) (NIST (National Institute of Standards and Technology)) Percent as parts per hundred, which is the divide-by-100 in the formula.

Background reading

Pages already listed as sources in this site's guides. They give context on inrush current and generator limits. None of them states this tool's equation or supplies a constant used above.

  1. Generator Sizing with an EasyStart Soft Starter - Calculation Examples (Micro-Air, Inc.) Worked generator sizing examples that start from continuous running load (RLA) and the other loads running at the same time.
  2. How and why to measure inrush current (Fluke) What inrush current is, and how breakers respond to it over time.
  3. Understanding Portable Generator Power Limits vs. Advertised Wattage (Generac) Starting watts and receptacle limits on portable generators.