For a 3-, 4-, or 5-ton central AC with a soft starter, start by comparing generators rated at 6,500, 7,500, or 9,000 running watts on gasoline, respectively, as examples to shortlist. Choose the size that covers your AC and other circuits while they run and can handle the compressor starting with those circuits already on. Generac standby generator sizing guide
Sizing examples by AC tonnage
The table screens the AC running load only for a 240 V single-phase system. The compressor estimates use ICM Controls’ average load ratings. Each row adds the outdoor fan (2 A) and indoor blower (3 A) from Micro-Air’s example. ICM Controls ICM870-32A specifications · Micro-Air EasyStart generator sizing examples
| Central AC | Estimated AC running current | Example portable generator | Gasoline running / starting watts (running amps at 240 V) | Propane running / starting watts (running amps at 240 V) |
|---|---|---|---|---|
| 3 ton | 16 + 2 + 3 = 21 A | Champion 201077 | 6,500 / 8,125 W (27.1 A) | 5,850 / 7,325 W (24.4 A) |
| 4 ton | 22 + 2 + 3 = 27 A | Champion 201281 | 7,500 / 9,375 W (31.3 A) | 6,750 / 8,400 W (28.1 A) |
| 5 ton | 26 + 2 + 3 = 31 A | Champion 201417 | 9,000 / 11,000 W (37.5 A) | 8,100 / 11,000 W (33.7 A) |
Estimate the AC running load
From the outdoor unit and indoor air handler or furnace nameplates or manuals, record the voltage, compressor RLA (run load amps), outdoor fan amps, and indoor blower amps. Add the currents as shown above when all three loads use the same voltage. If the blower uses a different voltage, give its volts and amps to your electrician as a separate load. ICM Controls ICM870-32A specifications · Micro-Air EasyStart generator sizing examples
Check startup and the loads that overlap
- Add up running watts. List the AC, the blower if rated separately, and any other loads you want on at the same time, such as a refrigerator, lights, or a well pump. Add their running wattages using the nameplates or manufacturer specs. Where you have only amps, record the voltage too for the electrician’s load calculation. Micro-Air EasyStart generator sizing examples · Generac standby generator sizing guide
- Get the startup demand with the soft starter installed. A compatible soft starter reduces the compressor’s starting surge. On the compressor nameplate, LRA stands for locked rotor amps. Give your HVAC technician the compressor and soft starter models and ask for an inrush measurement with the starter installed. Share that reading and the loads that will already be on with the generator supplier. Micro-Air EasyStart operating principle · Fluke motor inrush current guide · Generac standby generator sizing guide
- Check the overlap. Check the compressor’s startup demand alongside the loads already running. If a well pump can start with the compressor, have the installer account for both starts or set up load management. Confirm the proposed generator can start the AC with the planned backup loads. For whole-home standby, ask for a site survey and load calculation. Generac standby generator sizing guide
Check fuel and the home connection
- Use the rating for your fuel. The 201281’s propane running margin in the 4-ton example is 1.1 A (28.1 A − 27 A at 240 V). Check both running and starting ratings on the fuel you will use. Champion 201281 specifications · Micro-Air EasyStart generator sizing examples
- Check the outlet as well as the generator. The 5-ton example’s 31 A running estimate exceeds a 30 A connection. The 201417 also has a 37.5 A, 120/240 V receptacle. Ask your electrician to verify that the home connection can carry the planned load. Champion 201417 specifications · Generac standby generator sizing guide
- Run portable generators outdoors. Keep them well away from buildings, windows, doors, and vents. Generator exhaust contains carbon monoxide. Champion 201417 specifications
Evidence and limits. Manufacturer documentation for the ICM870 series, Micro-Air EasyStart, and the three listed Champion models was checked on November 27, 2026. The table combines published estimates and specifications. No equipment testing was performed.