ICM870-16A vs ICM870-32A Sizing and Compatibility

Use your compressor’s RLA to choose the ICM870-16A or ICM870-32A, then check whether CoreSense or Comfort Alert affects compatibility.

Choose the ICM870-16A for a compressor rated at 9.1 to 16 A RLA and the ICM870-32A for 16.1 to 32 A RLA. A Comfort Alert circuit board or kit in an air conditioner or heat pump rules out both. For the CoreSense Diagnostics module ICM describes, have an HVAC technician confirm whether a bypass is appropriate for your unit. ICM Controls compatibility and sizing notes

Match the soft starter to the compressor RLA

Find the compressor load amp rating (RLA) on the equipment’s service panel or in its user manual. Match that value to ICM’s published ranges below. ICM lists the same input specification for both the 16A and 32A models, 100 to 240 VAC at 50 or 60 Hz. ICM870-9A/16A specifications · ICM870-32A specifications

Compressor RLAICM model
Up to 9 AICM870-9A
9.1 to 16 AICM870-16A
16.1 to 32 AICM870-32A

For example, 16 A lands in the ICM870-16A range, while 16.1 A lands in the ICM870-32A range. ICM’s tonnage chart shows averages for single-phase air conditioners and heat pumps. Use the actual RLA before buying, and avoid moving up to the ICM870-32A just because the RLA is near the ICM870-16A limit. ICM Controls sizing chart

Check CoreSense and Comfort Alert compatibility

Identify the installed control before buying. ICM applies the same control restrictions to both starter sizes. ICM Controls control-board examples

Installed controlDecision before buying
Comfort Alert circuit board or kitSkip both sizes. ICM lists PCBHR105S, PCBHR10x and PCBGR10x as examples.
Emerson CoreSense Diagnostics module of the type ICM showsICM identifies this module as a bypass candidate. Have a technician review the exact unit and its safety circuits before proceeding.
Another air conditioner or heat pump control board that senses compressor current and locks out on faultsICM advises against using the ICM870 series with this type of board.

Give your technician the compressor RLA for sizing. Ask them to identify the control and confirm whether it senses compressor current and locks out on faults. Copeland lists CoreSense Diagnostics and CoreSense Protection as distinct products, so check the full module name. For an uncertain RLA match or a complex retrofit, ask your contractor to consult ICM. Copeland’s CoreSense lineup · ICM Controls Technical Support

Evidence and limits. ICM Controls’ ICM870-9A/16A and ICM870-32A product pages and technical guidance, along with Copeland’s residential CoreSense lineup, were checked on November 26, 2026. The comparison was prepared from documentation alone, without hands-on testing.